ID read stage model and serial number
IMM PGM MIP
USAGE ♦ ♦
SYNTAX ID ? or IDxx
PARAMETERS
Description xx [ int ] - axis number
Range xx - 1 to MAX AXES
Units xx - none
Defaults xx missing: error 37, AXIS NUMBER MISSING
out of range: error 9, AXIS NUMBER OUT OF RANGE
timeout: error 2, RS-232 COMMUNICATION TIME-OUT
DESCRIPTION This command is used to read and write (up to 16 character custom ID) Newport
ESP compatible positioner (stage) model and serial number.
Note:
An important information needed when asking for help with the motion control
system or when reporting a problem is the stage model and serial number. Use
this command to determine the positioner model and serial number.
RETURNS xx,yy
where: xx = model number
yy = serial number
REL. COMMANDS none
EXAMPLE 1 ID ? | read axis-1 positioner model and serial number
TS50DC.5, SN1263 | controller returns model and serial number
3-86 Section 3 – Remote Mode