Chapter 5
5-26
Remote I/O Functions
I/O Format (Allocated Words)
Outputs (PLC to Inverter) Instance ID: 101 Decimal (65 Hex)
SYSDRIVE 3G3MV
SYSDRIVE 3G3RV/3G3PV/3G3FV
Byte number Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Wd n Right-
most
0
Multi-
function
input 7
Multi-
function
input 6
Multi-
function
input 5
Multi-
function
input 4
Multi-
function
input 3
Reverse/
stop
For-
ward/sto
p
Left-
most
1Multi-
function
output 2
Multi-
function
output 1
Multi-
function
contact
output
Fault
reset
External
fault
input
Wd n+1 Right-
most
2 Frequency reference, rightmost byte
Left-
most
3 Frequency reference, leftmost byte
Wd n+2 Right-
most
4
Left-
most
5
Wd n+3 Right-
most
6
Left-
most
7
Byte number Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Wd n Right-
most
0Multi-
function
input 6
Multi-
function
input5
Multi-
function
input4
Multi-
function
input3
Multi-
function
input2
Multi-
function
input1
Reverse/
stop
For-
ward/sto
p
Left-
most
1Multi-
function
output 2
Multi-
function
output 1
Multi-
function
contact
output
Fault
reset
External
fault
input
Wd n+1 Right-
most
2 Frequency reference, rightmost byte
Left-
most
3 Frequency reference, leftmost byte
Wd n+2 Right-
most
4 Torque reference/torque limit, rightmost byte
Left-
most
5 Torque reference/torque limit, leftmost byte
Wd n+3 Right-
most
6 Torque compensation bias, rightmost byte
Left-
most
7 Torque compensation bias, leftmost byte