Chapter 4
4-7
SYSDRIVE Inverter Settings
4-2-2 Inverter Operation Command Selection
Select the method for inputting Run and Stop Commands to the Inverter. Select the method suit-
able for the application.
When operation commands (forward, reverse, stop) from the DeviceNet communications are to be
always used, set to “3."
Switching of Operation Commands from DeviceNet Communications
There is a switching signal, “Net. Ctrl.,” for operation commands from the standard remote I/O of the
DeviceNet Communications Card. The input method for operation commands can be changed in the
following ways using the “Net. Ctrl.” signal.
Net. Ctrl. = 1 (ON)
Enables operation commands from DeviceNet communications (remote I/O operation commands
become valid) regardless of the setting in b1-02.
Net. Ctrl. = 0 (OFF)
Enables the operation command setting in b1-02.
Parameter
No.
Set value Contents Default
setting
b1-02 0 Digital Operator RUN and STOP Keys on the Digital
Operator
1
1 Control circuit
terminals
Operation command input from control
circuit terminals
2 RS-422/485
communications
Operation commands received via RS-
422/485 communications
3 Optional Card Operation commands using DeviceNet
Communications Card