Chapter 4
4-7
SYSDRIVE Inverter Settings
4-2-2 Inverter Operation Command Selection
• Select the method for inputting Run and Stop Commands to the Inverter. Select the method suit-
able for the application.
• When operation commands (forward, reverse, stop) from the DeviceNet communications are to be
always used, set to “3."
■ Switching of Operation Commands from DeviceNet Communications
There is a switching signal, “Net. Ctrl.,” for operation commands from the standard remote I/O of the
DeviceNet Communications Card. The input method for operation commands can be changed in the
following ways using the “Net. Ctrl.” signal.
Net. Ctrl. = 1 (ON)
Enables operation commands from DeviceNet communications (remote I/O operation commands
become valid) regardless of the setting in b1-02.
Net. Ctrl. = 0 (OFF)
Enables the operation command setting in b1-02.
Parameter
No.
Set value Contents Default
setting
b1-02 0 Digital Operator RUN and STOP Keys on the Digital
Operator
1
1 Control circuit
terminals
Operation command input from control
circuit terminals
2 RS-422/485
communications
Operation commands received via RS-
422/485 communications
3 Optional Card Operation commands using DeviceNet
Communications Card