EasyManua.ls Logo

Omron 3G3MV-PDRT2 - Function Group 3 (N080 to N119)

Omron 3G3MV-PDRT2
363 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 10
10-38
Appendices
Function Group 3 (n080 to n119)
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex) Name Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
n080 0150 01 50 Carrier frequency selection 1 to 4, 7
to 9
1Differs
with
capacity.
No
n081 0151 01 51 Momentary power interruption com-
pensation
0 to 210No
n082 0152 01 52 Number of fault retries 0 to 10 1 0 No
n083 0153 01 53 Jump frequency 1 0.00 to
400.0
0.01 Hz 0.00 No
n084 0154 01 54 Jump frequency 2 0.00 to
400.0
0.01 Hz 0.00 No
n085 0155 01 55 Jump frequency 3 0.00 to
400.0
0.01 Hz 0.00 No
n086 0156 01 56 Jump width 0.00 to
25.50
0.01 Hz 0.00 No
n087 0157 01 57 Cumulative operation time selection 0, 1 1 0 No
n088 0158 01 58 Cumulative operation time 0 to 6550 1
(10 h)
0No
n089 0159 01 59 DC injection braking current 0 to 100 1% 50 No
n090 015A 01 5A DC injection braking-to-stop time 0.0 to
25.5
0.1 s 0.5 No
n091 015B 01 5B Startup DC injection braking time 0.0 to
25.5
0.1 s 0.0 No
n092 015C 01 5C Stall prevention during deceleration 0, 1 1 0 No
n093 015D 01 5D Stall prevention level during accelera-
tion
30 to 200 1% 170 No
n094 015E 01 5E Stall prevention level during operation 30 to 200 1% 160 No
n095 015F 01 5F Frequency detection level 0.00 to
400.0
0.01 Hz 0.00 No
n096 0160 01 60 Overtorque detection function selection
1
0 to 410No
n097 0161 01 61 Overtorque detection function selection
2
0, 110No
n098 0162 01 62 Overtorque detection level 30 to 200 1% 160 No
n099 0163 01 63 Overtorque detection time 0.1 to
10.0
0.1 s 0.1 No
n100 0164 01 64 UP/DOWN frequency selection 0, 1 1 0 No
n101 0165 01 65 Speed search deceleration time 0.0 to
10.0
0.1 s 2.0 No
n102 0166 01 66 Speed search level 0 to 200 1% 150 No
n103 0167 01 67 Torque compensation gain 0.0 to 2.5 0.1 1.0 Yes
n104 0168 01 68 Torque compensation primary delay
time constant
0.0 to
25.5
0.1 s 0.3 No
n105 0169 01 69 Torque compensation core loss 0.0 to
6550
0.1 W Differs
with
capacity.
No
n106 016A 01 6A Rated motor slip 0.0 to
20.0
0.1 Hz Differs
with
capacity.
Ye s
n107 016B 01 6B Motor phase-to-neutral resistance 0.000 to
65.50
0.001 Differs
with
capacity.
No

Table of Contents