Chapter 8
8-2
Communications Errors
8-1 Communications Line Errors
Malfunctions in DeviceNet communications that are a result of broken wires, short circuits, reversed
wiring, duplicate node address assignments, or noise interference are detected as transmission
(BUS) errors. When a transmission error is detected, the Inverter's Fault Bit will turn ON and the
motor will coast to a stop.
When an error is detected, perform error processing according to the indicator display of the
DeviceNet Communications Unit/Card with the terminal cover and Digital Operator removed.
Operation Indicators
The DeviceNet Communications Unit/Card has 2 operation indicators that show the status of the
power and communications.
Indicator Display Meaning Countermeasures
Color Status
MS Green Lit The Unit is operating normally. ---
Flashing Initial settings or necessary prepara-
tions for communications are incom-
plete.
Turn ON the Inverter power supply
again.
Replace the Option Unit.
Red Lit A fatal error (hardware error) has
occurred in the Unit.
Turn ON the Inverter power supply
again.
Replace the Option Unit.
Flashing A non-fatal error, such as a switch
setting error, has occurred.
Check the baud rate setting.
Turn ON the Inverter power supply
again.
Replace the Option Unit.
--- Not lit Power is not being supplied from the
Inverter.
The Unit is not connected properly
and power is not being to supplied to
it.
Check the Option Unit connector
and turn ON the Inverter power
supply.
Replace the Option Unit.