EasyManua.ls Logo

Omron 3G3MV-PDRT2 - Xw4 G-05 C4-Tf-D; Xw4 B-05 C4-Tf-D

Omron 3G3MV-PDRT2
363 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 3
3-18
Setup and Wiring
Thick Cables and Multi-drop Connections Using Multi-branch Parallel
Connectors
Multi-drop connections are possible when using 3G3MV-PDRT2 with an Inverter (except 5.5-kW or
7.5-kW models), by using the following connectors.
Note These connectors cannot be used with the following models. Use the T-branch Connectors
shown in 3-2-3 Connecting Communications Cables to T-branch Taps instead.
3G3MV Series (5.5-kW and 7.5-kW models)
•3G3RV Series
•3G3FV Series
3-2-6 Supplying Communications Power through T-branch Tap
When supplying the communications power supply through a T-branch Tap, attach the power supply
cables V+ and V- lines just like the communications lines. When there is a communications power
supply at just one point, connect the shield wire and ground line (100
max.) at the same time as
shown in the following diagram.
XW4G-05C4-TF-D XW4B-05C4-TF-D
(With set screws)
(Without set screws)
FG
FG
Communications cable
V
CAN H
Shield
CAN L
V+
Ground to 100 max.
(at one point only).
Communications
power supply
Ground to 100 max.
T-branch Tap or
Power Supply Tap
Communications
power supply
Ground to 100 max.

Table of Contents

Related product manuals