Chapter 5
5-33
Remote I/O Functions
5-7-2 Control I/O Remote I/O + Unit Status
This remote I/O setting is a default connection path setting, which attaches the 16-bit Unit status data
to the control I/O remote I/O function described in 5-6-1 Control I/O Remote I/O Operation. This sec-
tion explains the I/O format when the unit status is attached to the control I/O remote I/O.
For details on the function of specific input and output bits/bytes, refer to 5-6-1 Control I/O Remote
I/O Operation or 5-7-1 Unit Status.
■ I/O Format (Allocated Words)
● Outputs (PLC to Inverter) Instance ID: 101 Decimal (65 Hex)
SYSDRIVE 3G3MV
SYSDRIVE 3G3RV/3G3PV/3G3FV
Byte number Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Wd n Right-
most
0
Multi-
function 
input 7
Multi-
function 
input 6
Multi-
function 
input 5
Multi-
function 
input 4
Multi-
function 
input 3
Reverse/
stop
For-
ward/sto
p
Left-
most
1Multi-
function 
output 2
Multi-
function 
output 1
Multi-
function 
contact 
output
Fault 
reset
External 
fault 
input
Wd n+1 Right-
most
2 Frequency reference, rightmost byte
Left-
most
3 Frequency reference, leftmost byte
Wd n+2 Right-
most
4
Left-
most
5
Wd n+3 Right-
most
6
Left-
most
7
Byte number Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Wd n Right-
most
0Multi-
function 
input 6
Multi-
function 
input5
Multi-
function 
input4
Multi-
function 
input3
Multi-
function 
input2
Multi-
function 
input1
Reverse/
stop
For-
ward/sto
p
Left-
most
1Multi-
function 
output 2
Multi-
function 
output 1
Multi-
function 
contact 
output
Fault 
reset
External 
fault 
input