Chapter 10
10-68
Appendices
00 26 0026 Output cur-
rent
Monitors U1-03 (Inverters of 7.5 kW or less: 0.01-A units,
Inverters of 11 kW or more: 0.1-A units)
00 27 0027 Output
power
Monitors U1-08 (0.1-kW units)
--- --- 0028 to 002A Not used.
00 2B 002B Sequence input status
Bit 0 Multi-function input terminal S1 1: ON 0: OFF
Bit 1 Multi-function input terminal S2 1: ON 0: OFF
Bit 2 Multi-function input terminal S3 1: ON 0: OFF
Bit 3 Multi-function input terminal S4 1: ON 0: OFF
Bit 4 Multi-function input terminal S5 1: ON 0: OFF
Bit 5 Multi-function input terminal S6 1: ON 0: OFF
Bit 6 Multi-function input terminal S7 1: ON 0: OFF
Bits 7 to F Not used.
00 2C 002C Inverter status
Bit 0 Operation 1: Operating
Bit 1 Zero speed 1: Zero speed
Bit 2 Frequency matching 1: Matched
Bit 3 User-defined speed matching 1: Matched
Bit 4 Frequency detection 1 1: Output frequency
≤ L4-01
Bit 5 Frequency detection 2 1: Output frequency
≥ L4-01
Bit 6 Inverter startup completed 1: Startup completed
Bit 7 Low voltage detection 1: Detected
Bit 8 Baseblock 1: Inverter output baseblock
Bit 9 Frequency reference mode 1: Not communications 0: Com-
munications
Bit A Run command mode 1: Not communications 0: Communi-
cations
Bit B Overtorque detection 1: Detected
Bit C Frequency reference lost 1: Lost
Bit D Retrying error 1: Retrying
Bit E fault (including RS-422A/485 communications time-out) 1:
fault occurred
Bit F Communications time-out 1: Timed out
00 2D 002D Multi-function output status
Bit 0 Multi-function output (terminal M1-M2) 1: ON 0: OFF
Bit 1 Multi-function output (terminal M3-M4): 1: ON 0: OFF
Bits 2 to F Not used.
--- --- 002E to 0030 Not used.
00 31 0031 Main circuit
DC voltage
Monitors U1-07 (1-V units)
--- --- 0032 to 0037 Not used.
00 38 0038 PID feed-
back quantity
1% = 10; 100% = Input corresponding to max. output fre-
quency; without sign
Class 64 Register No.
(Hex)
Contents
In-
stance
At-
tribute