Chapter 10
10-59
Appendices
Note Values in parentheses are Asian model Inverters
■ External Terminal Function Parameters
F1-12 038B 03 8B Number of PG gear teeth 1 0 to 1000 1 0 No
F1-13 038C 03 8C Number of PG gear teeth 2 0 to 1000 1 0 No
F1-14 038D 03 8D PG open-circuit detection time 0.0 to
10.0
0.1 s 2.0 No
F4-01 0391 03 91 Channel 1 monitor selection 1 to 40 1 2 No
F4-02 0392 03 92 Channel 1 gain 0.00 to
2.50
0.01 1.00 Yes
F4-03 0393 03 93 Channel 2 monitor selection 1 to 40 1 3 No
F4-04 0394 03 94 Channel 2 gain 0.00 to
2.50
0.01 0.50 Yes
F4-05 0395 03 95 Channel 1 output monitor bias −10.0 to
10.0
0.1 0.0 Yes
F4-06 0396 03 96 Channel 2 output monitor bias −10.0 to
10.0
0.1 0.0 Yes
F4-07 0397 03 97 Analog output signal level for channel 1 0, 1 1 0 No
F4-08 0398 03 98 Analog output signal level for channel 2 0, 1 1 0 No
F5-01 0399 03 99 Not used. --- --- 0 No
F5-02 039A 03 9A Not used. --- --- 1 No
F5-03 039B 03 9B Not used. --- --- 2 No
F5-04 039C 03 9C Not used. --- --- 4 No
F5-05 039D 03 9D Not used. --- --- 6 No
F5-06 039E 03 9E Not used. --- --- 37 No
F5-07 039F 03 9F Not used. --- --- 0F No
F5-08 03A0 03 A0 Not used. --- --- 0F No
F5-09 03A1 03 A1 Not used. --- --- 0 No
F6-01 03A2 03 A2 DeviceNet fault operation selection 0 to 3 1 1 No
F6-02 03A3 03 A3 Communications external fault input
detection method selection
0, 110No
F6-03 03A4 03 A4 Communications external fault input
operation selection
0 to 3 1 1 No
F6-04 03A5 03 A5 Not used. --- --- 0 No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex) Name Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
H1-01 0400 04 00 Terminal S3 function selection 0 to 68 1 24 No
H1-02 0401 04 01 Terminal S4 function selection 0 to 68 1 14 No
H1-03 0402 04 02 Terminal S5 function selection 0 to 68 1 3 (0)
(See
note 1.)
No
H1-04 0403 04 03 Terminal S6 function selection 0 to 68 1 4 (3)
(See
note 1.)
No
H1-05 0404 04 04 Terminal S7 function selection 0 to 68 1 6 (4)
(See
note 1.)
No
H2-01 040B 04 0B Terminal M1-M2 Select 0 to 37 1 0 No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex) Name Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-