Chapter 6
6-10
Message Communications
6-5 Control Supervisor Objects: Class 29 Hex
Control supervisor objects are objects that have Inverter control I/O-related functions. They are
assigned according to their particular control I/O functions, such as forward operation, reverse oper-
ation, error detection, and so on. Be careful when setting up a remote I/O communications connec-
tion. These functions are shared with similar functions used for remote I/O, so even if they have been
set for message operations they may get rewritten for remote I/O.
Support Service Codes
Object Details
Service code number (hex) Service
0E Get attribute single
10 Set attribute single
05 Reset attribute: Can be sent to Class 29/Instance 01.
Turns OFF the Forward Operation and Reverse Operation inputs and turns
ON the Fault Reset. Then turns OFF the Fault Reset when Inverter Ready is
output.
Instance Attribute Name Content Setting range Default Read Write Size
00 01 Object Software
Revision
Indicates class 29 soft-
ware revisions. The revi-
sion value is advanced
whenever there is a
change.
--- 0001 Yes No Word
01 03 Forward/Stop 00: Stop
01: Forward operation
00, 01 00 Yes Yes Byte
04 Reverse/Stop 00: Stop
01: Reverse operation
00, 01 00 Yes Yes Byte
05 Net Control
Local/remote
switch
(See note 1.)
00: Operate with setting in
n003/b1-02.
01: Operate by DeviceNet
(not valid with 3G3FV)
00, 01 00 Yes Yes Byte
06 State
Inverter status
(See note 1.)
00 hex: Vendor specific
01 hex: Startup
02 hex: Not Ready
03 hex: ready
04 hex: Enabled
05 hex: Stopping
06 hex: Fault_Stop
07 hex: Faulted
--- 03 Yes No Byte
07 During forward
run
00: No Inverter output or
operating in reverse.
01: Forward operation or
DC braking
(Either DC braking from
reverse operation or oper-
ating forward.)
--- 00 Yes No Byte
08 During reverse
run
00: No Inverter output or
operating in forward.
01: Operating in reverse
(reverse operation output
status)
Becomes “00” with DC
braking.
--- 00 Yes No Byte