Chapter 6
6-11
Message Communications
Note 1. The following table shows the status of remote I/O output signals and operation indicated by
the content of Attribute 06 (State, i.e., Inverter status).
Note 2. The Net Control and Control From Net functions cannot be changed during running.
01
09 Inverter Ready 00: Preparing
Initial processing/ not
drive mode/ fault
01: Inverter ready
Inverter can receive run
command.
--- 00 Yes No Byte
0A Fault 00: Normal
01: Fault
--- 00 Yes No Byte
0B Alarm (minor
fault)
00: Normal
01: Alarm (minor fault)
--- 00 Yes No Byte
0C Fault Reset 00: Normal status
01: Fault reset
00, 01 00 Yes Yes Byte
0D Fault code Indicates the contents of
fault that occur. (See the
fault code list on the fol-
lowing page.)
--- 0000 Yes No Word
0F Control From
Net
Run signal input
status
(See note 2.)
00: Operating with an
n003/b1-02 setting other
than DeviceNet.
01: Operating by
DeviceNet.
--- 00 Yes No Byte
10 DeviceNet Fault
mode
(See note 3.)
00: Stop operation.
01: Continue operation.
02: Maker's specifications
3G3MV: 00,
01
3G3RV: ---
3G3FV: ---
3G3MV:
00
3G3RV:
02
3G3FV:
02
Ye s Ye s B y t e
11 Force Fault/Trip
Communica-
tions external
fault input
00: Normal operation
01: Communications
external fault input
00, 01 00 Yes Yes Byte
12 Force Status
Communica-
tions external
fault input status
00: Normal status
01: Communications
external fault detected.
(Inverter stopped with fault
detection.)
--- 00 Yes No Byte
Setting Status Condition
00 hex Vendor specific A condition other than the ones
below.
01 hex Startup: Preparation not complete (setting con-
stants)
Inverter Ready signal is OFF.
02 hex Not ready: Stopped (preparation complete) Inverter Ready signal is ON and Dur-
ing Run signal is OFF.
03 hex Inverter ready: Stopped (preparation complete) Inverter Ready signal is ON and Dur-
ing Run signal is OFF.
04 hex Enabled: Operating During Run signal (control I/O) is
ON.
05 hex Stopping: Decelerating (Operating with both
forward and reverse references equal to 0.)
Ctrl. From Net is ON, During For-
ward Run is OFF, During Reverse
Run is OFF, and During Run is ON.
06 hex Fault_Stop: Operating with fault detected Alarm signal is ON.
07 hex Faulted: Fault detected Fault signal is ON.
Instance Attribute Name Content Setting range Default Read Write Size