Chapter 10
10-63
Appendices
Note 1. Values in parentheses are for 400-V-class Inverters.
Note 2. If the setting is 0, the axis will accelerate to the specified speed over the specified acceler-
ation time (C1-01 to C1-08).
Note 3. The initial value when C6-01 is set to 1 is given. If C6-01 is set to 0, the initial value will be
150%.
Note 4. Values in parentheses are for Asian model Inverters.
Special Adjustment Parameters
Operator Parameters
L8-10 04B6 04 B6 Cooling fan control selection 0, 1 1 0 No
L8-11 04B7 04 B7 Cooling fan control delay time 0 to 300 1 s 60 No
L8-12 04B8 04 B8 Ambient temperature 45 to 60 1°C45 No
L8-15 04BB 04 BB OL2 characteristics selection at low
speeds
0, 111No
L8-18 04BE 04 BE Soft CLA selection 0, 1 1 1 No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex) Name Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
N1-01 0580 05 80 Hunting-prevention function selection 0, 1 1 1 No
N1-02 0581 05 81 Hunting-prevention gain 0.00 to
2.50
0.01 1.00 No
N2-01 0584 05 84 Speed feedback detection control
(AFR) gain
0.00 to
10.00
0.01 1.00 No
N2-02 0585 05 85 Speed feedback detection control
(AFR) time constant
0 to 2000 1 ms 50 No
N2-03 0586 05 86 Speed feedback detection control
(AFR) time constant 2
0 to 2000 1 ms 750 No
N3-01 0588 05 88 High-slip braking deceleration fre-
quency width
1 to 20 1% 5 No
N3-02 0589 05 89 High-slip braking current limit 100 to
200
1% 150 No
N3-03 058A 05 8A High-slip braking stop dwell time 0.1 to
10.0
0.1 s 1.0 No
N3-04 058B 05 8B High-slip braking OL time 30 to
1200
1 s 40 No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex) Name Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute
o1-01 0500 05 00 Monitor selection 4 to 33 1 6 Yes
o1-02 0501 05 01 Monitor selection after power up 1 to 4 1 1 Yes
o1-03 0502 05 02 Frequency units of reference setting
and monitor
0 to
39999
10No
o1-05 0504 05 04 LCD brightness 0 to 5 1 3 Yes
o2-01 0505 05 05 LOCAL/REMOTE key enable/disable 0, 1 1 1 No
o2-02 0506 05 06 STOP key during control circuit termi-
nal operation
0, 111No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex) Name Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute