Chapter 10
10-62
Appendices
L2-06 048A 04 8A KEB deceleration time 0.0 to
200.0
0.1 s 0.0 No
L2-07 048B 04 8B Momentary recovery time 0.0 to
25.5
0.1 s 0.0 (See
note 2.)
No
L2-08 048C 04 8C Frequency reduction gain at KEB start 0 to 300 1 100 No
L3-01 048F 04 8F Stall prevention selection during accel 0 to 2 1 1 No
L3-02 0490 04 90 Stall prevention level during accel 0 to 200 1% 120 (See
note 3.)
No
L3-03 0491 04 91 Stall prevention limit during accel 0 to 100 1% 50 No
L3-04 0492 04 92 Stall prevention selection during decel 0 to 3 1 1 No
L3-05 0493 04 93 Stall prevention selection during run-
ning
0 to 211No
L3-06 0494 04 94 Stall prevention level during running 30 to 200 1% 120 (See
note 3.)
No
L4-01 0499 04 99 Speed agreement detection level 0.0 to
400.0
0.1 Hz 0.0 No
L4-02 049A 04 9A Speed agreement detection width 0.0 to
20.0
0.1 Hz 2.0 No
L4-03 049B 04 9B Speed agreement detection level (+/) 400.0 to
400.0
0.1 Hz 0.0 No
L4-04 049C 04 9C Speed agreement detection width (+/) 0.0 to
20.0
0.1 Hz 2.0 No
L4-05 049D 04 9D Operation when frequency reference is
lost
0, 110No
L4-06 04C2 04 C2 Frequency reference for loss of fre-
quency reference
0.0 to
100.0
0.1% 80.0 No
L5-01 049E 04 9E Number of auto restart attempts 0 to 10 1 0 No
L5-02 049F 04 9F Auto restart operation selection 0, 1 1 0 No
L6-01 04A1 04 A1 Torque detection selection 1 0 to 8 1 0 No
L6-02 04A2 04 A2 Torque detection level 1 0 to 300 1% 150 No
L6-03 04A3 04 A3 Torque detection time 1 0.0 to
10.0
0.1 s 0.1 No
L6-04 04A4 04 A4 Torque detection selection 2 0 to 8 1 0 No
L6-05 04A5 04 A5 Torque detection level 2 0 to 300 1% 150 No
L6-06 04A6 04 A6 Torque detection time 2 0.0 to
10.0
0.1 s 0.1 No
L7-01 04A7 04 A7 Forward drive torque limit 0 to 300 1% 200 No
L7-02 04A8 04 A8 Reverse drive torque limit 0 to 300 1% 200 No
L7-03 04A9 04 A9 Forward regenerative torque limit 0 to 300 1% 200 No
L7-04 04AA 04 AA Reverse regenerative torque limit 0 to 300 1% 200 No
L8-01 04AD 04 AD Protect selection for internal DB resis-
tor
0, 110No
L8-02 04AE 04 AE Overheat pre-alarm level 50 to 130 1°C Depends
on
capacity.
No
L8-03 04AF 04 AF Operation selection after overheat pre-
alarm
0 to 313No
L8-05 04B1 04 B1 Input open-phase protection selection 0, 1 1 1 (0)
(See
note 4.)
No
L8-07 04B3 04 B3 Output open-phase protection selec-
tion
0, 110No
L8-09 04B5 04 B5 Ground protection selection 0, 1 1 1 No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex) Name Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute