Use the shortest ground wire possible. For 400-V Inverters, ground the neutral point on the power
supply. Ground the metal control panel (and doors) at the same time.
Use a shielded cable for the cable between the Inverter and motor as well. Keep the cable as short
as possible (20 m max.) and ground the shield at both ends of the cable. It is effective to mount a
clamp filter right next to the Inverter's output terminals.
Use a conductive cable clamp to directly ground the shield to the ground plate.
Ground the motor frame directly and connect the ground from the motor directly to the EMC-compli-
ant input noise filter.
Use a ZCAT3035-1330 Clamp Filter on the communications cable, wind the cable in a loop around
it, and keep it away from the control panel.
Use conductive packing on the doors of the control panel to increase shielding.
Do not mount any wireless or other devices designed to generate electromagnetic waves.
Use reinforced insulation or double insulation for the DC power supply for communications.
The Inverter's control terminals have only basic insulation. Further insulation must be provided if
the terminals are wired to a device that will ultimately come in contact with people.
Grounding the Shield
Cable clamp
(conductive)
Shield mesh
Ground plat
e