Chapter 10
10-88
Appendices
Alarm 2: Register Number 001A Hex
Inverter Monitoring: U1-@@
12 EF7 External fault (terminal 7)
13 EF8 External fault (terminal 8)
14 --- Not used.
15 OS Overspeed
Bit Display Content
0 DEV Speed deviation
1 PGO PG is disconnected
2 to 15 --- Not used.
Class 64 Register
number
Monitor
number
Monitored item Output unit
Instance Attribute
00 20 0020 U1-01 Frequency reference Set in o1-03
00 21 0021 U1-02 Output frequency Set in o1-03
00 22 0022 U1-03 Output current 8192 decimal = Inverter
rated current
00 23 0023 U1-04 Control method Set in A1-02
00 24 0024 U1-05 Motor speed Set in o1-03
00 25 0025 U1-06 Output voltage 0.1 V
00 26 0026 U1-07 Main circuit DC voltage 1 V
00 27 0027 U1-08 Output power 0.1 kW
00 28 0028 U1-09 Torque reference 0.1%
00 29 0029 U1-10 Input terminal status Bits 0 to 7 = terminals 1 to 8
00 2A 002A U1-11 Output terminal status (Refer to table below.)
00 2B 002B U1-12 Operating status (Refer to table below.)
00 2C 002C U1-13 Elapsed time 1 hour
00 2D 002D U1-14 FLASH ID software No. ---
00 2E 002E U1-15 Terminal 13 level 0.1% (100% = 10 V)
00 2F 002F U1-16 Terminal 14 level 0.1% (100% = 20 mA)
00 30 0030 U1-17 Terminal 16 level 0.1% (100% = 10 V)
00 31 0031 U1-18 Motor secondary current 0.1% (100%: Motor rated
current)
00 32 0032 U1-19 Motor excitation current 0.1% (100%: Motor rated
current)
00 33 0033 U1-20 Output frequency after a soft
start
Set in o1-03
00 34 0034 U1-21 Input to speed control loop 0.01% (100%: Maximum fre-
quency)
00 35 0035 U1-22 Output from speed control
loop
0.1% (100%: Motor rated
current)
Bit Display Content