H2-02 040C 04 0C Terminal P1 function select (open col-
lector)
0 to 3711No
H2-03 040D 04 0D Terminal P2 function select (open col-
lector)
0 to 3712No
H3-01 0410 04 10 Signal select terminal A1 (voltage)
(See note 4.)
0 or 110No
H3-02 0411 04 11 Frequency reference (voltage)
gain (terminal A1)
0.0 to
1000.0
0.1% 100.0 Yes
H3-03 0412 04 12 Frequency reference (voltage)
bias (terminal A1)
−100.0 to
100.0
0.1% 0.0 Yes
H3-08 0417 04 17 Multi-function analog input terminal A2
signal level selection
0 to 212No
H3-09 0418 04 18 Multi-function analog input terminal A2
function selection
0 to 1F10No
H3-10 0419 04 19 Frequency reference (current)
gain (terminal A2)
0.0 to
1000.0
0.1% 100.0 Yes
H3-11 041A 04 1A Frequency reference (current)
bias (terminal A2)
−100.0 to
100.0
0.1% 0.0 Yes
H3-12 041B 04 1B Analog input filter time constant 0.00 to
2.00
0.01 s 0.00 No
H3-13 041C 04 1C Terminal A1/A2 switching 0, 1 1 0 No
H4-01 041D 04 1D Multi-function analog output 1 monitor
selection (terminal FM)
1 to 4012No
H4-02 041E 04 1E Multi-function analog output 1gain (ter-
minal FM)
0.0 to
1000.0
(0.00 to
2.50)
(see
note 3.)
0.1%
(0.01)
(See
note 3.)
100.0
(1.00)
(See
note 3.)
Ye s
H4-03 041F 04 1F Multi-function analog output 1 bias (ter-
minal FM)
−110.0 to
110.0
(−10.0 to
10.0)
(See
note 3.)
0.1% 0.0 Yes
H4-04 0420 04 20 Multi-function analog output 2 monitor
selection (terminal AM)
1 to 4013No
H4-05 0421 04 21 Multi-function analog output 2 gain (ter-
minal AM)
0.0 to
1000.0
(0.00 to
2.50)
0.1%
(0.01)
(See
note 3.)
50 (0.50)
(See
note 3.)
Ye s
H4-06 0422 04 22 Multi-function analog output 2
bias (terminal AM)
−110.0 to
110.0
(−10.0 to
10.0)
(See
note 3)
0.1% 0.0 Yes
H4-07 0423 04 23 Multi-function analog output 1 signal
level selection
0, 1, 2
(0, 1)
(See
note 3.)
10No
H4-08 0424 04 24 Multi-function analog output 2 signal
level selection
0, 110No
H5-01 0425 04 25 Slave address 0 to 20
(See
note 2.)
11FNo
H5-02 0426 04 26 Communication speed selection 0 to 4 1 3 No
H5-03 0427 04 27 Communication parity selection 0 to 2 1 0 No
Con-
stant
Regis-
ter num-
ber
(hex)
Class 64 (hex) Name Setting
range
Setting
unit
Default
setting
Write
during
opera-
tion
In-
stance
At-
tribute