Chapter 10
10-69
Appendices
00 39 0039 PID input
quantity
1% = 10; 100% = Max. output frequency; without sign
00 3A 003A PID output
quantity
1% = 10; 100% = Max. output frequency; without sign
00 3B 003B CPU software number
00 3C 003C Flash software number
00 3D 003D Communications error details
Bit 0 CRC error
Bit 1 Invalid data length
Bit 2 Not used.
Bit 3 Parity error
Bit 4 Overrun error
Bit 5 Framing error
Bit 6 Time-out
Bits 7 to F Not used.
00 3E 003E kVA setting
00 3F 003F Control method
00 40 0040 Frequency
reference
Monitors U1-01; 0.01-Hz units (units set in o1-03; with sign)
00 41 0041 Output fre-
quency
Monitors U1-02; 0.01-Hz units (units set in o1-03; with sign)
00 42 0042 Output cur-
rent
Monitors U1-03; % units: 8192 at rated current
--- --- 0043 and
0044
Not used.
00 45 0045 Output volt-
age
Monitors U1-06; 0.1-V units
00 46 0046 Main circuit
DC voltage
Monitors U1-07; 1-V units
00 47 0047 Output
power
Monitors U1-08; 0.1-kW units (with sign)
--- --- 0048 Not used.
00 49 0049 Input termi-
nal status
Monitors U1-10; 1: ON. Bits 0 to 6 correspond to terminals
S1 to S7.
00 4A 004A Output termi-
nal status
Monitors U1-11
Bit 0 Terminals M1 and M2; 1: ON
Bit 1 Terminals M3 and M4; 1: ON
Bits 2 to
6
Not used.
Bit 7 Terminals MA and MC; 1: ON
Bits 8 to
F
Not used.
Class 64 Register No.
(Hex)
Contents
In-
stance
At-
tribute