Chapter 5
5-34
Remote I/O Functions
● Inputs (Inverter to PLC) Instance ID: 152 Decimal (98 Hex)
Note 1. A shaded box indicates that the bit is not used.
Note 2. Control remote I/O inputs and outputs are paired. When using control remote I/O, be sure
to set them together.
Note 3. Control remote I/O objects do not conform to the AC/DC drive profile, but are specially set
for this product.
Wd n+1 Right-
most
2 Frequency reference, rightmost byte
Left-
most
3 Frequency reference, leftmost byte
Wd n+2 Right-
most
4 Torque reference/torque limit, rightmost byte
Left-
most
5 Torque reference/torque limit, leftmost byte
Wd n+3 Right-
most
6 Torque compensation bias, rightmost byte
Left-
most
7 Torque compensation bias, leftmost byte
Byte number Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
Wd m Right-
most
0 Fault Alarm
(minor
fault)
Inverter
ready
At refer-
ence
During
reset
input
During
reverse
run
Zero
speed
During
run
Left-
most
1P
lock/com
pletion
(See
note 4.)
Multi-
function
output 2
Multi-
function
output 1
Multi-
function
contact
output
Local/re
mote
UV
detected
Opera-
tion fault
Wd m+1 Right-
most
2 Output frequency monitor, rightmost byte
Left-
most
3 Output frequency monitor, leftmost byte
Wd m+2 Right-
most
4 Torque reference monitor, rightmost byte
Left-
most
5 Torque reference monitor, leftmost byte
Wd m+3 Right-
most
6 Output current monitor, rightmost byte
Left-
most
7 Output current monitor, leftmost byte
Wd m+4 Right-
most
0 Con-
nected
compo-
nent
mainte-
nance
flag
Opera-
tion time
over flag
Warning
torque
detected
flag
Cooling
fan/elec-
trolytic
capaci-
tor main-
tenance
flag
Inverter
unit
mainte-
nance
flag
Network
power
voltage
drop flag
Left-
most
1 Error flag Inverter detected fault code
Byte number Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0