Chapter 7
7-69
Configurator Settings
7-5-6 Current Trace Tab Page
■ History Tab Page
Item Details Reference
Time Displays the time determined from the current trace sampling cycle. 7-2-4 Current Trace
Current Displays all the traced current levels for every sampling cycle.
Status Displays whether the sampling timing is during acceleration/deceleration or
frequency agreement.
Trigger Set the signal used for trace timing.
Note: The trace is performed using the trigger setting combined with the
Start Trigger Button, Middle Trigger Button, and End Trigger Button.
Current Trace Sam-
pling Cycle
Select the trace sampling cycle from the pull-down menu.
Note: The cycle can be set to 10 ms, 20 ms, 50 ms, 100 ms, up to 100 s.
Trace Button Starts the trace.
Note: The trace will continue until the Cancel Button is clicked. The 150
points sampled immediately before the Cancel Button is clicked will be
stored.
Trace (Buffer Full)
Button
Starts a trace that will stop when 150 points are sampled.
Note: The trace will also stop if the Cancel Button is clicked during the
trace.
Cancel Button Stops the trace.
Start Trigger Button The trace stops when 150 points have been sampled using the trigger sig-
nal selected in the Trigger field.
Note: The trace will also stop if the Cancel Button is clicked during the
trace.
Middle Trigger But-
ton
Starts a trace that will stop when 75 points have been sampled using the
trigger signal selected in the Trigger field.
Note 1: The 75 points from immediately before and after the trigger are
sampled.
Note 2: The trace will also stop if the Cancel Button is clicked during the
trace.
End Trigger Button Starts a trace that stops at the trigger signal selected in the Tr i g ge r field.
Note 1: The 150 points from immediately before the trigger are sampled.
Note 2: The trace will also stop if the Cancel Button is clicked during the
trace.
Save Button Converts traced data into CSV format and saves in a file.