Chapter 10
10-19
Appendices
01 0F Power Actual Can be referenced in hexa-
decimal with the output
power monitor U-11/U1-08
minimum unit as 1 W.
Setting the attribute 1A
power scale enables a mul-
tiplication factor to be set.
--- 0000 Yes No Word
10 Input Voltage Can be referenced in hexa-
decimal with the input volt-
age setting (200 or 400/E1-
01) minimum unit as 1 V.
Setting the attribute 1B volt-
age scale enables a multi-
plication factor to be set.
--- 0000 Yes No Word
11 Output Voltage Can be referenced in hexa-
decimal with the output volt-
age monitor U-04/U1-06
minimum unit as 1 V.
Setting the attribute 1B volt-
age scale enables a multi-
plication factor to be set.
--- 0000 Yes No Word
12 Accel Time Can be set and read in
hexadecimal with the accel-
eration time 1 n019/C1-01
and deceleration time 1
n020/C1-02 minimum unit
as 1 ms.
Depending on the accelera-
tion/ deceleration time unit
n018/C1-10 setting, num-
bers below 100 ms or 10
ms are truncated.
Setting the attribute 1C time
scale enables a multiplica-
tion factor to be set.
0.0 to 6,000.0
(0.00 to
600.00
2710 hex
(10.0 s)
Ye s Ye s Wo r d
13 Decel Time 2710 hex
(10.0 s)
Ye s Ye s Wo r d
14 Low Speed Limit
(See notes 2, 3,
and 4.)
Can be set and read in
hexadecimal with the fre-
quency reference lower limit
n034/d2-02 and the fre-
quency reference upper
limit n033/d2-01 minimum
unit as 1 ms.
The minimum unit can be
set by the frequency refer-
ence setting and display
units in n035/o1-03.
n035/o1-03 = 0: 0.01 Hz
n035/o1-03 = 1: 0.01%
(100%: Max. frequency.)
n035/o1-03 = 2 to 39:
1r/min
n035/o1-03 = 40 to 3,999:
Follow individual set values.
When r/min units are being
used, a multiplier can be set
in attribute 16 (the Speed
Scale setting).
0 to 109% of
maximum fre-
quency
0000 Yes Yes Word
15 High Speed
Limit
(See notes 2, 3,
and 4.)
0 to 110% of
maximum fre-
quency
0708 hex
(1,800 r/
min)
Ye s Ye s Wo r d
16 Speed scale Speed data unit selection
can be set and read. The
speed data unit value is cal-
culated as follows:
Unit = 1 [r/min] x 1/2
a
a: Speed scale set value
Set a negative value as its
2's complement.
−15 to 15 (F1
to 0F hex)
00 Yes Yes Byte
Instance Attribute Name Content Setting range Default Read Write Size