EasyManua.ls Logo

Omron 3G3MV-PDRT2 - Page 303

Omron 3G3MV-PDRT2
363 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 10
10-45
Appendices
00 2C 002C Inverter status
Bit 0 Operation 1: Operating
Bit 1 Zero speed 1: Zero speed
Bit 2 Frequency agreement 1: Agreement
Bit 3 User-defined speed agreement 1: Agreement
Bit 4 Frequency detection 1 1: Output frequency
L4-01
Bit 5 Frequency detection 2 1: Output frequency
L4-01
Bit 6 Inverter startup completed 1: Startup completed
Bit 7 Low voltage detection 1: Detected
Bit 8 Baseblock 1: Inverter output baseblock
Bit 9 Frequency reference mode 1: Not communications 0:
Communications
Bit 10 Run command mode 1: Not communications 0: Com-
munications
Bit 11 Overtorque detection 1: Detected
Bit 12 Frequency reference lost 1: Lost
Bit 13 Retrying error 1: Retrying
Bit 14 Fault. (including RS-422A/485 communications time-
out) 1: fault occurred
Bit 15 Communications time-out 1: Timed out
00 2D 002D Multi-function output status
Bit 0 Multi-function contact output (terminals M1-M2) 1:
ON 0: OFF
Bit 1 Multi-function PHC output 1 (terminals P1-PC): 1: ON
0: OFF
Bit 2 Multi-function PHC output 2 (terminals P2-PC): 1: ON
0: OFF
Bit 3 to 15 Not used.
--- --- 002E to 0030 Not used.
00 31 0031 Main circuit DC voltage Monitors U1-07 (1-V units)
--- --- 0032 to 0037 Not used.
00 38 0038 PID feedback
quantity
1% = 10; 100% = Input corresponding to max. output
frequency; without sign
00 39 0039 PID input
quantity
1% = 10; 100% = Max. output frequency; without sign
00 3A 003A PID output
quantity
1% = 10; 100% = Max. output frequency; without sign
00 3B 003B CPU software number
00 3C 003C Flash software number
Class 64 Register
number (hex)
Content
Instance Attribute

Table of Contents

Related product manuals