EasyManua.ls Logo

Omron 3G3MV-PDRT2 - Page 92

Omron 3G3MV-PDRT2
363 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 4
4-12
SYSDRIVE Inverter Settings
Note 1. Be sure to set F9-05 to 0 when using flux vector control. If used with the default setting (1),
the torque reference/torque limit will be interpreted as zero and there will be no torque output
unless there is a torque reference/torque limit from control I/O remote I/O.
Note 2. If F9-06 is set to 3 (continues operating), the Inverter will continue operating when a com-
munications fault occurs according to the contents of settings immediately before. Be sure
to take any steps necessary to ensure safety, such as installing a limit switch or an emer-
gency stop switch.
F9-03 Communications external fault
input: operation
Select the Inverter operation per-
formed when there is a communi-
cations external fault input from
communications (DeviceNet Com-
munications Card).
0: Decelerates to a stop using C1-
02 deceleration time/fault detec-
tion
1: Coats to a stop/fault detection
2: Decelerates to a stop using the
C1-09 emergency stop time/
fault detection
3: Continues operating/alarm
detection
0 to 3 1
EFO Fault Action
F9-04 Not used Do not set. --- 0
Trace Sample Tim
F9-05 Torque reference/torque limit
selection from communications
When operating in flux vector con-
trol mode, this setting enables or
disables torque reference and
torque limit values input from com-
munications (DeviceNet Communi-
cations Card). (See note 1.)
0: Torque reference/torque limit
from communications disabled.
1: Torque reference/torque limit
from communications enabled.
0, 1 0
Torq Ref/Lmt Sel
F9-06 Communications fault opera-
tion
Select the Inverter operation per-
formed when a communications
fault is detected.
0: Decelerates to a stop using C1-
02 deceleration time/fault detec-
tion
1: Coats to a stop/fault detection
2: Decelerates to a stop using the
C1-09 emergency stop time/
fault detection
3: Continues operating/alarm
detection (See note 2.)
0 to 3 1
BUS Fault Sel
Parameter
No.
Name Contents Setting
range
Default
setting
Operator display

Table of Contents