3-6 Parameter List
3
Operation
Electronic thermal
b013
Electronic thermal
characteristics
selection
00: Reduced torque characteristics 1
01: Constant torque characteristics
02: Reduced torque characteristics 2
00
No ⎯
10AE
4-32
b213
*2nd electronic
thermal
characteristics
selection
00 1528
Overload limit
b021
Overload limit
selection
00: Disabled
01: Enabled in acceleration/constant speed
operation
02: Enabled in constant speed operation
01
No ⎯
10B5
4-33
b221
*2nd overload limit
selection
01 1529
b022 Overload limit level
0..1 × Rated current to 1.5 × Rated current
1.5 ×
Rated
current
No A
10B6
4-33
b222
*2nd overload limit
level
1.5 ×
Rated
current
152A
b023
Overload limit
parameter
0.1 to 3000.0
1.0
No s
10B7
4-33
b223
*2nd overload limit
parameter
1.0 152B
b028
Overload limit source
selection
00: b022, b222 set values
01: Input terminal O
00
No ⎯
10BB
4-33
b228
*2nd overload limit
source selection
00 152C
Active Freq Match
b029
Deceleration rate
constant at Active
Frequency Matching
restart
0.1 to 3000.0 0.5 No s 1171 4-30
b030
Active Frequency
Matching restart level
0.2 × Rated current to 2.0 × Rated current
Rated
current
No A 1172 4-30
Lock
b031 Soft lock selection
00: Data other than b031 cannot be changed
when terminal SFT is ON.
01: Data other than b031 and the specified
frequency parameter cannot be changed when
terminal SFT is ON.
02: Data other than b031 cannot be changed.
03: Data other than b031 and the specified
frequency parameter cannot be changed.
10: Data other than parameters changeable
during operation cannot be changed.
01 No ⎯ 10BC 4-35
Non-stop at momentary power interruption
b050
Selection of non-stop
function at
momentary power
interruption
00: Disabled
01: Enabled (Stop)
02: Enabled (Restart)
00 No 10C9 4-36
b051
Starting voltage of
non-stop function at
momentary power
interruption
0.0 to 1000. 0.0 No V 10CA 4-36
b052
Stop deceleration
level of non-stop
function at
momentary power
interruption
0.0 to 1000. 0.0 No V 10CB 4-36
Parameter
No.
Function name
Monitor or data range
(Digital Operator)
Default
setting
Change
during
Run
Unit
Modbus
Address
(Hex)
Page