3-6 Parameter List
3
Operation
Non-stop at momentary power interruption
b053
Deceleration time of 
non-stop function at 
momentary power 
interruption
0.01 to 99.99
100.0 to 999.9
1000 to 3000
1.0 No s 10CC 4-36
b054
Deceleration starting 
width of non-stop 
function at 
momentary power 
interruption
0.0 to 10.0 0.0 No Hz 10CE 4-36
Others
b055
Overvoltage 
protection 
proportional gain 
during deceleration
0.2 to 5.0 0.2 Yes ⎯ 1173 4-37
b056
Overvoltage 
protection integral 
time during 
deceleration
0.0 to 150.0 0.2 Yes s 1174 4-37
b080 AM adjustment
0. to 255.
(Shared with C086 for AM offset adjustment)
100. Yes ⎯ 10CF
4-39
4-62
b082 Starting frequency 0.5 to 9.9 1.5 No Hz 10D1 4-39
b083 Carrier frequency 2.0 to 12.0 3.0 No kHz 10D2
4-40
4-63
Initialization
b084 Initialization selection
00: Clears the trip monitor
01: Initializes data
02: Clears the trip monitor and initializes data
00 No ⎯ 10D3 4-41
b085
Initialization 
parameter selection
00
* Do not change.
00 No ⎯ 10D4 4-41
Others
b086
Frequency 
conversion 
coefficient
0.1 to 99.9 1.0 Yes ⎯ 10D5 4-41
b087 STOP key selection
00: Enabled
01: Disabled
00 No ⎯ 10D6 4-41
b088
Free-run stop 
selection
00: 0 Hz start
01: Active Frequency Matching restart
00 No ⎯ 10D7 4-41
b089
Monitor display 
selection
01: Output frequency monitor
02: Output current monitor
03: Rotation direction monitor
04: PID feedback value monitor
05: Multi-function input monitor
06: Multi-function output monitor
07: Frequency conversion monitor
01 Yes ⎯ 10D8 4-42
b091 Stop selection
00: Deceleration → Stop
01: Free-run stop
00 No ⎯ 10DA 4-41
b092 Cooling fan control
00: Always ON
01: ON during RUN
02: Depends on the fin temperature
01 No ⎯ 10DB 4-43
b130
Overvoltage LAD 
stop function
00: Disabled
01: Enabled
00 No ⎯ 10F5 4-38
Parameter 
No.
Function name
Monitor or data range
(Digital Operator)
Default 
setting
Change 
during 
Run
Unit
Modbus 
Address 
(Hex)
Page