RIGOL 2 Command System
2-262 MSO2000A/DS2000A Programming Guide
[:TRACe<n>]:DATA:LOAD?
Syntax
[:TRACe<n>]:DATA:LOAD? 1
Description
Read the specified data packet in the volatile memory of the built-in signal source.
Parameter
Name Type Range Default
<n> Discrete {1|2} 1
[:TRACe<n>]:DATA:POINts
Syntax
[:TRACe<n>]:DATA:POINts VOLATILE, {<point>|MINimum|MAXimum}
[:TRACe<n>]:DATA:POINts? VOLATILE[,MINimum|MAXimum]
Description
Set or query the number of arbitrary waveform initial points of the specified built-in signal source channel.
Parameter
Name Type Range Default
<point> Integer 2 to 16384 2
<n> Discrete {1|2} 1
Explanation
This command sets the amplitude of the initial points to 0 automatically.
Return Format
The query returns an integer between 2 and 16384.
Example
:DATA:POINts VOLATILE,200