I/O Expander: Output Parameters
Activates when the source of the Main Panel's AC power is interrupted. This
activation will follow the delay time defined in the system control times and
the AC Off Delay Time parameter.
Activates the Utility Output after any bell burglary alarm in any partition in
the system.
The utility output will follow the predefined time programming that is defined
in the scheduler of the weekly programs for utility output activation.
Activates the utility output when a Tamper occurs in the system.
Activates the Utility Output when a duress alarm is initiated by any user
defined as duress code.
Activates the utility output when there is GSM trouble in the GSM.
This output is activated once an Entry Bypass timer starts (see page 34). The
output is designed to be part of the bypass keypad solution for the Danish
market. The output behavior depends on the output pattern as follows:
Pulsed: Use this option to activate an electronic lock. The time duration is as
defined by the installer under Pulse Duration Length (see page 81).
Latched: While the system is disarmed, entering a bypass code will activate the
output like an access control reader. Output operation using the bypass code
during disarm mode will not be registered in the event log.
During Away (Full Arm) mode, opening an Open Delay zone (during the
Entry Bypass time) will shorten the output time to 3 seconds.
Activates the utility output when a door button is pressed on a slim keypad.
This output operates only as a pulse output (as defined by Pulse Duration
Length (see page 81).