110 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023
Chapter 6 Troubleshoot the System
Alert 2054 Cannot reset the terminal in Safe mode.
Terminal restart is disabled on the emulator. Select Flash>Save
and then select File>Reset>Hard to restart the emulator.
Alert 2055 Image exceeds maximum resolution of 800x800. Open file in image editor and reduce the resolution.
Alert 2056 Cannot copy recipe to a loaded application. Unload application and try again.
Alert 2057
Terminal is running low on application memory
(<Available_Virtual_Memory>bytes).
Reset the terminal or this may lead to fatal error.
Alert 2058
Failed setting property: /*S:0 Param1*/::/*S:0 Param2*/, value
= /*S:0 Param3*/
Verify the range of the numeric display that uses the external tag
as its write tag is within the range of a tag (validation should
provide a warning if the range of the tag is greater than the range
of a numeric entry). Make sure that the values of the state-based
objects that write to an external tag are within the range of the
tag. Make sure that the value that written to an external tag
matches the tag type (for example, do not write a non-numeric
string into a numeric tag).
Make sure that the Ethernet port is enabled.
Alert 2059
Failed setting property (/*S:0 Param1*/): /*S:0 Param2*/::/*S:0
Param3*/, value = /*S:0 Param4*/
Verify the range of the numeric display that uses the external tag
as its write tag is within the range of a tag (validation should
provide a warning if the range of the tag is greater than the range
of a numeric entry). Make sure that the values of the state-based
objects that write to an external tag are within the range of the
tag. Make sure that the value that written to an external tag
matches the tag type (for example, do not write a non-numeric
string into a numeric tag).
Alert 2060 Terminal is running low on RAM (<Available_RAM>bytes). Reset the terminal or this may lead to fatal error.
Alert 2061
Out of memory: Terminal cannot continue to run and will be
reset.
This is a out of memory critical message. Dismissing this dialog
causes the terminal to reset.
After the terminal resets, try to edit an application and reduce its
size by removing some objects, for example, user controls,
screens, tags, or alarms.
Alert 2062 Cannot copy recipe to a loaded application. Unload application and try again.
Alert 2064 Cannot enter Safe Mode while terminal security is enabled. Disable terminal security and try again.
Alert 2065 Table has changed. Do you want to continue? Press Yes to continue with the changed Recipe table.
Alert 2066 Logging Error
Make sure that a microSD card or USB device is connected to the
terminal to store the datalog.
Alert 2067 Invalid filename Make sure that the filename is valid.
Alert 2068 Only one Trend with data logging is allowed.
Make sure that the application only has one Trend with data
logging.
Alert 2069 Landscape Orientation. Confirm Restart? Select No to restart later.
Alert 2070 Portrait Orientation. Confirm Restart? Select No to restart later.
Alert 2071
Application was designed for a different Orientation and may
not appear or operate as intended. Continue?
Press Yes to continue, or No to cancel. Then change the
orientation of the application in Connected Components
Workbench software to match the terminal and try again.
Alert 2072
Application was designed for a different Platform type and
Orientation, and may not appear or operate as intended.
Continue?
Press Yes to continue, or No to cancel. Then change the catalog
of the application in Connected Components Workbench software
to match the terminal and try again.
Alert 2073
Non-validated application is not supported for CompactLogix
controller. Validate before loading
Validate the application and correct any validation errors, save
the application, then try again.
Alert 2074 Terminal encountered an exception and will reboot
This message is for informational purposes. No corrective action
needed.
Alert 2075 Application will be unloaded. Confirm (Y/N)? Press Yes to unload the application.
Alert 2076
This application does not have at least one Goto Config button.
Set as Startup Application?
Press Yes to continue setting the application as a startup
application, or No to cancel. Edit the application and make sure
that there is at least one Goto Config button.
Alert 2077 Controller Settings cannot be changed for running application. Stop the application and try again.
Alert 2078
Controller address cannot conflict with PanelView 800
terminal Station Address.
Make sure that the controller address is different from the
PanelView 800 terminal station address.
Alert 2079
CompactLogix controller based application must contain valid
path.
Make sure that a valid path exists and try again.
Alert 2080
Invalid View-Only password. Password should not contain any
special character.
Make sure that the View-Only password does not contain any
special characters.
Alert 2081 Old password does not match with terminal.
Make sure that the correct password is entered in the Old
Password field.
PanelView 800 Terminal Alerts (Continued)
Category ID Description Corrective Action