76 Rockwell Automation Publication 2711R-UM001I-EN-E - February 2023
Chapter 3 DesignStation in Connected Components Workbench Software
Allen-Bradley Micro800 CIP Ethernet Communication
Allen-Bradley Micro800 CIP Ethernet Communication Parameters
Parameter Description Value
Controller Settings
Name Enter a unique name for the controller.
Any valid character
(a…z, A…Z, and 1…9)
Controller Type The type of controller to connect to.
Micro800
(cannot be changed)
Address
Enter the unique IP address of the controller on the
Ethernet network.
xxx.xxx.xxx.xxx
Where x is a number from 0…9
Description Enter an optional description for the controller.
Any valid character
(a…z, A…Z, and 1…9)
Response Timeout
Milliseconds
Specify how long the terminal waits for the controller to
respond to a communication request.
100…30000
Connection Timeout
Seconds
Specify how long the terminal waits to establish a socket
connection to a remote controller.
1…60
Fail After
Specify the number of times the terminal repeats the
communication request before the request is considered
a failed attempt, and the controller is in error.
1…10
PanelView 800 Settings
No configurable parameters are available for this communication protocol.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation Allen-Bradley PanelView 800 and is the answer not in the manual?

Rockwell Automation Allen-Bradley PanelView 800 Specifications

General IconGeneral
BrandRockwell Automation
ModelAllen-Bradley PanelView 800
CategoryTouch terminals
LanguageEnglish

Related product manuals