Page #23 background image
General Installation Information 1-7
PowerFlex® 700L Liquid-Cooled Drive User Manual
Publication 20L-UM001D-EN-P
CE Conformity
Compliance with the Low Voltage (LV) Directive and Electromagnetic
Compatibility Directive (EMC) has been demonstrated using harmonized
European Norm (EN) standards published in the Official Journal of the
European Communities. PowerFlex 700L Liquid-Cooled AC drives comply
with the EN standards listed below when installed according to this
PowerFlex 700L Liquid-Cooled AC Drive User Manual, PowerFlex 700
Active Converter User Manual, PowerFlex 700 - Series B User Manual or
PowerFlex 700S Phase II Control User Manual, and PowerFlex 70/700
Reference Manual.
CE Declarations of Conformity are available online at: www.ab.com/
certification/ce/docs
Low Voltage Directive (2006/95/EC)
EN50178 Electronic equipment for use in power installations.
EMC Directive (2004/108/EC)
EN61800-3 Adjustable speed electrical power drive systems - Part 3:
EMC requirements and specific test methods.
General Notes
Without additional external filtering, PowerFlex 700L Liquid-Cooled
AC drives satisfy the 2nd Environment high-frequency emission limits of
EN61800-3. Without external mitigation, PowerFlex 700L
Liquid-Cooled drives are not intended to be used on a low-voltage public
network which supplies residential or office premises; radio frequency
interference is expected if used in such an environment.
The drive motor cable should be kept as short as possible in order to
minimize electromagnetic emission and capacitive currents.
Use of line filters in ungrounded systems is not recommended.
Conformity of the drive with CE EMC requirements does not guarantee
an entire machine or installation complies with CE EMC requirements.
Many factors can influence total machine/installation compliance.
Non-regenerative PowerFlex 700L Liquid-Cooled AC drives generate
conducted low frequency disturbances (harmonic emissions) on the AC
supply system which may require mitigation in some applications. More
information regarding harmonic emissions can be found in the
PowerFlex 70/700 Reference Manual (publication PFLEX-RM001).
When operated on a public supply system, it is the responsibility of the
installer or user to ensure, by consultation with the distribution network
operator and Rockwell Automation, if necessary, that applicable
requirements have been met.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 700 and is the answer not in the manual?

Rockwell Automation PowerFlex 700 Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 700
CategoryController
LanguageEnglish

Related product manuals