Programming and Parameters 5-3
PowerFlex® 700L Liquid-Cooled Drive User Manual
Publication 20L-UM001D-EN-P
Communication File
For the following Communication file parameters, Bit 6 is available and will
be set when DPI port 6 is indicated.
File
Group
No. Parameter Name & Description Values
COMMUNICATION
Comm Control
274 [DPI Port Sel]
Selects which DPI port reference value will appear in [DPI Port Value].
Default:
Options:
1
1 - 6
“DPI Port 1”
“DPI Port 1 - 6”
Masks & Owners
276 [Logic Mask]
Determines which ports can control the drive when [Write Mask Act], bit 15 is set to “1.” If the bit for a port is set to “0,the port will
have no control functions except for stop.
277 [Start Mask]
Controls which adapters can issue start commands.
See [Logic Mask]
278 [Jog Mask]
Controls which adapters can issue jog commands.
See [Logic Mask]
279 [Direction Mask]
Controls which adapters can issue forward/reverse commands.
See [Logic Mask]
280 [Reference Mask]
Controls which adapters can select an alternate reference; [Speed Ref A, B Sel] or
[Preset Speed 1-7].
See [Logic Mask]
281 [Accel Mask]
Controls which adapters can select [Accel Time 1, 2].
See [Logic Mask]
282 [Decel Mask]
Controls which adapters can select [Decel Time 1, 2].
See [Logic Mask]
283 [Fault Clr Mask]
Controls which adapters can clear a fault.
See [Logic Mask]
284 [MOP Mask]
Controls which adapters can issue MOP commands to the drive.
See [Logic Mask]
285 [Local Mask]
Controls which adapters are allowed to take exclusive control of drive logic
commands (except stop). Exclusive “local” control can only be taken while the drive is
stopped.
See [Logic Mask]
288 [Stop Owner]
Adapters that are presently issuing a valid stop command.
Read Only
289 [Start Owner]
Adapters that are presently issuing a valid start command.
See [Stop Owner]
290 [Jog Owner]
Adapters that are presently issuing a valid jog command.
See [Stop Owner]
Bit
Definition
DPI Port 6
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Digital In
Default xxxxxxxxx1111111
Bit 1514131211109876543210
1 = Control Permitted
0 = Control Masked
x = Reserved
Bit
Definition
DPI Port 6
DPI Port 5
DPI Port 4
DPI Port 3
DPI Port 2
DPI Port 1
Digital In
Default xxxxxxxxx1111111
Bit 1514131211109876543210
1 = Issuing Command
0 = No Command
x = Reserved

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation PowerFlex 700 and is the answer not in the manual?

Rockwell Automation PowerFlex 700 Specifications

General IconGeneral
BrandRockwell Automation
ModelPowerFlex 700
CategoryController
LanguageEnglish

Related product manuals