TROUBLESHOOTING
OVERVIEW
Table 7-1 below gives information on the possible causes of system
malfunctions. It also lists the symptoms and necessary actions to be taken.
Table 7-1. Troubleshooting
chart
Symptom Possible cause Action
No level reading
Power disconnected
Data communication cables
disconnected
Check the power supply
Check the cables for serial data communication
Check LED/Display
No HART communication
COM Port configuration does
not match the connected COM
Port
Cables may be disconnected
Wrong HART address is used
Hardware failure
HART resistor
Check that correct COM Port is selected in the HART
server (see “Specifying the COM Port” on page 5-14)
Check the COM port buffer, “Specifying the COM Port”
on page 5-14
Check wiring diagram
Verify that the 250 Ohm resistor is in the loop, see
Figure 4-10 on page 4-10
Check cables
Make sure that correct HART short address is used. Try
address=0
Check the COM Port Buffer setting, see page 5-14
Check Analog Output current value to verify that
transmitter hardware works
Analog Out is set in Alarm
Measurement Failure or
Transmitter Failure
Open the Diagnostics window in RRM to check active
errors and alarms, see Diagnostics” on page 7-17
See also “Analyzing the Measurement Signal” on
page 7-4 and “Analog Output Status” on page 7-26
Incorrect level reading
Configuration error
Disturbing objects in the tank
See “Application Errors” on
page 7-27
Check the Tank Height parameter; RRM>Setup>Tank
Check status information and diagnostics information,
see “Diagnostics” on page 7-17
Check that the transmitter has not locked on an
interfering object
See “Analyzing the Measurement Signal” on page 7-4
Integral display does not work
Check the display configuration in Rosemount Radar
Master (open menu Setup>General)
Diagnostics
Contact Emerson Process Management Service
Department
(1)
Temperature Measurement
Failure
Check ambient temperature
(2)
Restart gauge
Contact Emerson Process Management Service
Department
Level Measurement Failure
Check Power Supply
Check the gauge configuration
Check that the mechanical installation is correct
Volume Measurement Failure
Restart gauge
Check gauge configuration using PC Based
configuration tool
No surface echo
Check signal strength
Restart transmitter
See “Analyzing the Measurement Signal” on page 7-4
(1) A malfunctioning display panel may only be replaced by service personnel at Emerson Process Management Service Department.
(2) If the 5400 transmitter has been exposed to temperatures outside the specified limits, the device may stop its normal operation.