Hardware Configuration PR 5610 Installation Manual
40 Sartorius
3.4.5 PR 1713/08 BCD output
This option card for is preferably used in the slot 3 (installation see chapter 3.2.1), because otherwise plugs for
other cards are blocked. It does not make use of the terminal blocks A/B.
The card can be used only in connection with an application package supporting it or with a program written in
IEC 61131. Binary data needs to be decoded by the program for a BCD output.
Connecting method: 2-row 25-pin connector
28 pole connector (20 + 8 pole plug)
Number of outputs:
Number of inputs:
Output: 24 bit binary, corresponding
to 6 BCD decades. Input: 1bit.
Output stage:
Common collector connected to
+Uext., open emitter
External Supply: +5 V ... +24 V, max. 32 V
Voltage drop: Approx. 1.7 V
Output current: Max. 50 mA
Input (enable): 5 V / 24 V jumper selectable
5 V high > 3.1 V, low < 1.5 V
24 V high > 16 V, low < 10V
protected against wrong polarity
Dimension (LxWxH): 80 x 68 x 15 mm Potential isolation: no
Weight: 40 grs. Cable length (screened): Max. 50 m
• Accessory: 27 pole connection cable, 3m with plugs 20 pole and 8 pole at one side
Plug and connection cable (Output bit: %QXn.m., n-slot, m-bit):
%QXn.0 black 1 2 brown %QXn.1
%QXn.2 red 3 4 orange %QXn.3
%QXn.4 yellow 5 6 green %QXn.5
%QXn.6 blue 7 8 violet %QXn.7
%QXn.8 grey 9 10 white %QXn.9
%QXn.10 white - black 11 12 white - brown %QXn.11
%QXn.12 white - red 13 14 white - orange %QXn.13
%QXn.14 white - yellow 15 16 white - green %QXn.15
%QXn.16 white - blue 17 18 white - violet %QXn.17
%QXn.18 white - grey 19 20 brown - black %QXn.19
%QXn.20 brown - red 1 2 brown - orange %QXn.21
%QXn.22 brown - yellow 3 4 brown - green %QXn.23
Enable brown - blue 5 6 brown - violet Uext
GND brown - grey 7 8 free
If PR 1713/08 is used as BCD-output for weight values, the
output bits of the 6th decade can be used as follows:
%QXn.20
SIGN sign bit
%QXn.21 STSTI standstill bit
%QXn.22 ERROR error bit
%QXn.23 DAHOL data valid