Commissioning PR 5610 Installation Manual
96 Sartorius
4.8.3.11 Lines per Recipe
With lines per recipe the maximum number of component lines in a recipe is defined.
Enter the number of requested lines per recipe form [1] to [255]
with numeric keys; confirm with
.
4.8.3.12 Recipe simulation
The recipe simulation calculates whether the amounts of components in a recipe are exceeding the range 0 to
FSD. If this is the case, Error 19 will be generated and the recipe will not start.
Select the recipe simulation [enabled] or [disabled] with or
; confirm with .
4.8.3.13 Subrecipe
The subrecipe is used, if certain component sequences are used in several recipes. The subrecipe is called like a
component in a recipe.
Select the subrecipe function [enabled] or [disabled] with
or
; confirm with .
4.8.4 Fieldbus parameter
This section appears only, if a PR 1721/xx module is inserted in slot 4. Select protocol, parameter and operating
mode for the optional fieldbus interface PR 1721/xx.
Enter with .
4.8.4.1 PR 1721 protocol
Select the fieldbus protocol [Interbus-S] for ../12, [Profibus-DP]
for ../11 or [DeviceNet] for ../14 with
or ; confirm with
.
Dependent on selection, further parameters are required, e.g.:
[Interbus-S]
Enter update interval from [1] to [50] with numerical keys;
confirm with .
*The actualization interval has to be calculated according to the following formula:
1000 / (15 + number of bytes + 0.3 x number of slaves).