10
Error diagnostics for operation on EtherNet/IP™ and Modbus/TCP
Fieldbus timeout
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
117
10.4 Fieldbus timeout
WARNING
Risk of crushing if the drive keeps running unintentionally after a communication
timeout or fault elimination.
Severe or fatal injuries or damage to property.
Note that the communication timeout resets automatically as soon as communic-
ation with the lower-level device is reestablished. That is, the drives receive the
current process output data from the PLC straight away after system bus com-
munication restarts.
Disconnect the drive controller from the power supply before rectifying a fault if
automatic restart of the driven machine after fault elimination is not permitted for
safety reasons.
A fieldbus timeout can occur in device when you switch off the fieldbus master or if
there is a wire break in the fieldbus cabling:
The "S1" LED indicates that no new user data is being received.
The process data for all subordinate devices has been set to Value"0". This means
that all drives connected to the device are stopped.
The digital outputs are set to "0".
16998413/EN – 12/2016