Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
196
13.7.2 Parameter group 1: Setpoints / ramp generators
The following settings are defined in this parameter group:
• Speed ramps
• Fixed speed setpoints
P13./P14. Speed ramps1/2
P130–P133 / P140–P143 ramp t11 / t21 up/down CW/CCW
Setting range: 0–2–2000s
Specifically, the parameters are:
• P130 Rampt11 up CW / P140 Rampt21 up CW
• P131 Rampt11 down CW / P141 Rampt21 down CW
• P132 Rampt11 up CCW / P142 Rampt21 up CCW
• P133 Rampt11 down CCW / P143 Rampt21 down CCW
The ramp times refer to a setpoint step change of Δn=3000min
-1
. The ramp takes ef-
fect when the speed setpoint is changed and the enable signal is revoked via the CW/
CCW terminal.
18364786955
[1] Ramp up CW
[2] Ramp down CW
[3] Ramp up CCW
[4] Ramp down CCW
P134/P144 Rampt12/t22 UP=DOWN
Setting range: 0–10–2000s
The following applies to this ramp: UP=DOWN and CW=CCW.
Rampst12/t22 are activated via a digital input(→2215), which is programmed with
the function "Speed ramp switchover".
16998413/EN – 12/2016