Process data description
Process image of MOVIPRO® ADC with R15regenerative power supply
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
132
11.4.3 Configuring regenerative power supply
The R15 regenerative power supply is commissioned as an axis in the Application
Configurator controller software.
Proceed as follows:
1. Start the Application Configurator and create a new configuration.
2. Insert a single axis into the configuration. Click on the symbol [1].
18150926859
ð A new line is displayed in the axis area.
3. Specify the following settings for the axis:
Window element Setting/value
Name Name of the axis
Controller interface IO
Axis address 1
Device type R15
Application module Regenerative power supply1PD
Number of process data 1
4. Click the button [2].
ð After successful configuration, a green check mark appears at the end of the
line.
5. Then configure the desired CCU application module.
ð In this example, the "Transparent6PD" CCU application module is configured.