Ethernet Industrial Protocol (EtherNet/IP™)
Technical data of the EtherNet/IP™ interface
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
89
7.5.3 Timeout response of "explicit messages"
The timeout status is triggered by the EtherNet/IP™ slave. The EtherNet/IP™ master
sets the timeout interval while establishing a connection. The EtherNet/IP™ specifica-
tion refers to an "Expected packet rate" rather than a timeout interval in this case. The
"Expected Packet Rate" is calculated from the timeout delay as follows:
t
t
Expected Packet Rate ExplicitMessages
Timeout ExplicitMe
_ _ _
_
=
sssages
4
The "Expected Packet Rate" sets the "Forward Open Telegram" when the connection
is established.
If a timeout occurs for the "explicit messages", the connection type is dropped auto-
matically in the default setting of the EtherNet/IP™. The connection type must be re-
established to communicate with "explicit messages" again. The timeout is not forwar-
ded to the IEC program.
7.6 Technical data of the EtherNet/IP™ interface
EtherNet/IP™ MOVIPRO
®
Automatic
baud rate detection
10MBd/100MBd
Connection technology M12 (D-coded)
Integrated switch Supports auto-crossing, auto-negotiation.
Maximum line length 100m according to IEEE Std 802.3, 200 Edi-
tion
Addressing
4 byte IP address or MAC-ID
(00-0F-69-xx-xx-xx)
Configurable via DHCP server or
MOVITOOLS
®
MotionStudio with version 5.6
and higher
Address default value: 192.168.10.4
Vendor ID 013B
hex
Name of EDS files SEW_MOVIPRO.EDS
Name of icon files SEW_MOVPRO.ICO