13
Parameter setting
Parameter descriptions
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
195
P08. Fault memory
P080–P084 Faults t-0–t-4
The device has 5 fault memories (t-0 to t4-). The faults (→2224) are saved in chro-
nological sequence. The last fault result is stored in the fault memory t-0. In the case
of more than 5 faults, the oldest fault result is deleted from the fault memory t-4.
The following information is stored and displayed when an error occurs:
• Status ("0" or "1") of the digital inputs/outputs
• Operating status of the device
• Inverter status
• Cooling air temperature
• Speed
• Output current
• Active current
• Device utilization
• DC link voltage
• Operating hours
• Enable hours
• Parameter set
• Motor utilization 1 and 2
P09. Bus diagnostics
P094–P096 PO1–PO3 setpoint
Currently transferred value of the process output data words (→ 2 229) in hexa-
decimal form
P097–P099 PI1–PI3 actual value
Currently transferred value of the process input data words (→2230) in hexadecimal
form
16998413/EN – 12/2016