11
Process data description
MOVIPRO® ADC process sequence
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
124
MOVIPRO
®
ADC status word (2bytes)
Bit Meaning Coding and function
8–15 Device status/warning/error number
Bits 8 – 15 are assigned depending on the value of bits
6 and 7 (see the following table).
Bits 8–15 of the MOVIPRO
®
ADC status word are assigned as follows:
Bits 8–15 of the MOVIPRO
®
ADC status word
Bit 6 Bit 7 Meaning Coding and function
0 0 Device status
0 = System start-up
1 = Ready
10 = Data backup
Dataset is uploaded from the MOVIPRO
®
ADC to
the SD memory card.
11 = Data backup
Dataset successfully uploaded from
MOVIPRO
®
ADC to SD memory card.
12 = Data backup
Dataset is downloaded from the SD memory card
to MOVIPRO
®
ADC.
13 = Data backup
Dataset successfully downloaded from SD memory
card to MOVIPRO
®
ADC.
1 0 Warning
0 1 Error number
1 = Configuration
No connection to power section "PFA-...".
2 = Error external I/O
3 = Configuration
No IPOS
PLUS®
application module available.
4 = Process data stopped to lower-level devices
(gateway).
10 = Configuration
No configuration available.
11 = Configuration
Unable to establish connection with configured
devices.
20 = Data backup
Upload failed.
21 = Data backup
Upload failed because SD memory card is write-
protected.
22 = Data backup
Download failed.
23 = Data backup
STO safety function required.
99 = Internal system error
110 = Overload actuator voltage DO00
120 = Overload sensor voltage group 1
121 = Overload sensor voltage group 2
16998413/EN – 12/2016