13
Parameter setting
Parameterizing the power section "PFA-..."
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
159
Commencing startup
WARNING
Risk of crushing from uncontrolled start-up of the motor, if the start-up is aborted due
to using an inadmissible version of the MOVITOOLS
®
MotionStudio engineering
software.
Severe or fatal injuries.
• Always use MOVITOOLS
®
MotionStudio V6.20version or later.
INFORMATION
There is no need to activate the factory settings.
If you call up a factory setting, the "PFA‑..." power section parameters will be reset to
the default values.
Proceed as follows:
ü You have installed the MOVITOOLS
®
MotionStudio engineering software on the
engineering PC, V6.20 or later.
ü The drive can be run in order to be able to measure the translation ratio between
the motor and encoder, e.g. by means of the "manual mode" plug-in.
ü The following installations are correct and the application is executed accordingly:
Wiring, terminal assignment, safety shutdowns
1. In the network view of MOVITOOLS
®
MotionStudio, select the Power section.
2. Choose the command [Startup] > [Startup] from the context menu.
ð The startup assistant for encoder startup is displayed. Follow the instructions of
the startup assistant. You can switch between the dialogs by using the [Back]
and [Next] buttons.
18014401534132875
16998413/EN – 12/2016