13
Parameter setting
Parameter descriptions
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
233
P903 Reference travel type
Setting range: 0–8
Reference travel strategy with which the machine zero of a system is specified. This
defines a travel mode for searching for a reference cam, for example.
This parameter also specifies the search direction for the reference cam in the indi-
vidual referencing phases.
Use parameter P904 Referencing to zero pulse (→2234) to determine if the refer-
ence travel takes place to the edge change of the reference cam or the next zero
pulse of the encoder.
An operationally ready and enabled drive is prerequisite for carrying out the reference
travel. The reference travel type8 is an exception.
The following reference travel types are possible:
Type 0: CCW zero pulse
First search direction: CCW
Reference point: CCW zero pulse from current position
Machine zero: Reference position+reference offset
Type 1: CW end of the reference cam
First search direction: CCW
Reference point: First zero pulse or falling edge to the left of the reference cam
Machine zero: Reference position+reference offset
Type 2: CW end of the reference cam
First search direction: CW
Reference point: First zero pulse or falling edge to the right of the reference
cam
Machine zero: Reference position+reference offset
Type 3: CW limit switch
First search direction: CW
Reference point: First zero pulse or falling edge to the left of the right limit
switch
Machine zero: Reference position+reference offset
Reference travel should take place to zero pulse.
Type 4: Limit switch left
First search direction: CCW
Reference point: First zero pulse or falling edge to the right of the left limit
switch
Machine zero: Reference position+reference offset
Reference travel should take place to zero pulse.
Type 5: No reference travel
Reference point: Current position (referencing with drive enable)
Machine zero: Reference offset
Type 6: Reference cam flush with CW limit switch
First search direction: CW
Reference point: First zero pulse or falling edge to the left of the reference cam
16998413/EN – 12/2016