6
Configuration and startup of EtherNet/IP™
Project planning examples
Manual – MOVIPRO
®
with EtherNet/IP™ or Modbus/TCP Fieldbus Interface
53
Access to device parameters without DLR support with RSLogix 5000 up to versionV19
The following example describes the configuration of read and write access to the
device parameters with RSLogix5000, VersionV19.
Reading parameters
Proceed as follows:
1. Create the user-defined data type "SEW_Parameter_Channel". It allows you to or-
ganize the process data in a structure and simplifies access to the data elements.
INFORMATION
To ensure proper operation of the parameter channel, you must not change the order
of the variables. The data types must also match the figure.
9007214912527883
2. Create the following controller tags:
Name Data structure
ReadParameter MESSAGE
ReadParameterRequest SEW_Parameter_Channel
ReadParameterResponse SEW_Parameter_Channel
ReadParameterStart BOOL
16998413/EN – 12/2016