EasyManua.ls Logo

SICK FLOWSIC600 - Page 109

SICK FLOWSIC600
262 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
FLOWSIC600 · Technical Information · 8010125 V 4.0 · © SICK AG 109
Subject to change without notice
Figure 51 Terminal assignment for use in safe areas
Terminal box
Power supply Field connections (10-pole terminal block)
PE
PE
NOTICE: Potential equalization
PE: Potential Equalization terminal must be connected to earth ground.
NOTICE: Device-internal bridge
Terminals 2 and PE are bridged internally, i.e. there is no insulation between PE
and negative potential (
Figure 50).
This bridge is a firm part of the device and mandatory. It must not be
removed or altered.
Altering the bridge voids the manufacturer's warranty.
NOTICE: Termination of Modbus lines
Begin and end of the Modbus lines must be terminated.
Terminal 81/82: Always terminated
Terminal 33/34: Switchable, terminated ex factory
For detailed information, see Service Manual FLOWSIC600, Section 4.4 "Serial
interface RS485".

Table of Contents

Other manuals for SICK FLOWSIC600

Related product manuals