152 FLOWSIC600 · Technical Information · 8010125 V 4.0 · © SICK AG
Commissioning
Subject to change without notice
Monitored event
Configurable User
Warning parameters
Default
value
Notes
Default
activation
state
1
High gas velocity VOG limit 45 m/s If the current average Velocity of Gas exceeds the value "VOG
limit", a User Warning is generated.
Caution:
This parameter (Reg. #7201"MaxVelGas") also defines the
upper limit of the gas velocity range classes for the Diagnostics
Comparison Log. Changes to this parameter will clear all data
from the Diagnostics Comparison Log.
Configure "VOG limit" to suit the specific application.
Off
Power supply
(low input voltage)
Input voltage warning 12000mV If the power supply voltage drops below the value "Input volt-
age warning" (e.g. in applications with autarkic power supply
by solar panels) a User Warning is generated.
Off
A Logbook is full
of unackn. entries
Logbook full of unack. entries If one of the logbooks is full of unacknowledged entries, a User
Warning is generated.
Off
Meter is in Config-
uration Mode
Warning at Configuration Mode If the meter is in Configuration Mode, a User Warning is gener-
ated.
Off
Battery lifespan Warning if battery lifespan is low If the remaining battery lifespan is less than 15%, a User Warn-
ing is generated.
On
1
User Warnings must be activated to become effective on the warning output.
2
These user warning limits are only monitored, as long as certain preconditions are met (see
Table 22).
Table 20 System warnings