Operating instructions Chapter 4
S300
8010948/YY96/2016-02-17 © SICK AG • Industrial Safety Systems • Germany • All rights reserved 55
Subject to change without notice
Configurable functions
The function can be realized with the aid of the park mode or the stand-by mode.
If, in an EFI system, you only use the OSSDs on one safety laser scanner (common OSSDs),
t
hen the OSSDs on this safety laser scanner will switch to the OFF state as soon as either
of the two safety laser scanners is switched to the park/stand-by mode. If, on the other
hand, you use the OSSDs on both safety laser scanners (separate OSSDs), then only the
OSSDs on the safety laser scanner that is switched to park/stand-by mode will switch to
the OFF state.
Park mode
To switch to the park mode, configure a monitoring case for which the park mode is
defined in the CDS.
The S300 needs the response time resulting from the configuration to switch from the
park mode to another monitoring case.
Stand-by mode
A dedicated STBY single-channel input is provided for switching to the stand-by mode
(see section 6.1.1 “Pin assignment on the system plug” on page 82).
Alternatively it is also possible to switch to the stand-by mode via EFI (see section 12.5
“EFI status information and control commands” on page 129).
A monitoring case is not occupied by the stand-by mode.
4.11 Measured data output
For the measured data output configure the baud rate of the interface.
You configure whether the Silent time is set automatically to 5000 ms or you configure an
individual shorter Silent time between 60 and 4980 ms. The silent time defines the time,
after sending the silent byte, for which the continuous output of data can be interrupted to
make it possible to access to the interface. In the default delivery status, the Silent time is
set to 5000 ms.
With the aid of the Send mode option you can configure whether the measured dataoutput
is to be triggered as a Continuous data output or Data output only on request.
You will find further details on this topic in the “Telegram Listing Standard” documentation
(part no. 9090807).
CMS functionality on the S300 Expert
On the S300 Expert you can configure additional parameters for the CMS functionality.
With the aid of the Send mode option you can configure whether the measured data out-
put is to be triggered as a Continuous data output, Data output only on request or by an
Internal event.
If you have selected Internal event, then you must define this event.
With Continuous data output you must select which data are to be output.
If you also activate Measured data output, then you can select whether the measured
data are to be output together with the I/O data in one telegram or in two separate
telegrams.
For the measured data output you define one to five segments (which are defined by start
and end angles).
You will find further details on this topic in the “Telegram Listing CMS” documentation
(part no. 9090806).
Note
Note

Table of Contents

Other manuals for SICK S300

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SICK S300 and is the answer not in the manual?

SICK S300 Specifications

General IconGeneral
Protection ClassIP65
Resolution30 mm
InterfaceRS-422, Ethernet
Power Supply24 V DC
Operating Temperature0 °C ... +50 °C

Related product manuals