Chapter 6 Operating instructions
S300
84 © SICK AG • Industrial Safety Systems • Germany • All rights reserved 8010948/YY96/2016-02-17
Subject to change without notice
Electrical installation
6.2 System plug assembly
T
he system plug has cable entries for cable glands on the underside and on the rear. The
number of cable entries and cable glands varies depending on the variant:
system plug SX0B-A0000G for S300 Standard and S300 Advanced:
1 cable entry with M16 cable gland
1 cable entry without M16 cable gland (blanking plug)
2 cable entries without M12 cable gland (blanking plugs)
system plug SX0B-A0000J for S300 Professional and Expert:
1 cable entry with M16 cable gland
1 cable entry without M16 cable gland (blanking plug)
6 cable entries without M12 cable gland (blanking plugs)
2 M12 cable glands, enclosed loose
You can also procure the S300 with pre-assembled system plug with varying cable lengths
(see section 6.3 “Pre-assembled system plugs” on page 86 and section 13.3.2 “System
plug S300” on page 136).
The length of the spare cable should be such that the system plug cannot inadvertently
be plugged into a neighboring S300!
From experience 20 to 30 cm spare cable at the safety laser scanner have proven to be
adequate. In this way you avoid the inadvertent connection of the system plug to a neigh-
boring S300 and operation of an S300 with an incorrect configuration. The spare cable
enables you to change the S300 with ease if necessary.
Note
WARNING
Fig.
57
:
System plug
SX0B6A0000G for
S300 Standard and
S300 Advanced
Fig.
58
:
System plug
SX0B6A0000J for S300
Professional and Expert