Binary Input Points
Static (Steady-State) Object Number: 1 (Packed Format)
Change Event Object Number: 1 (w/o Time)
Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)
or 2 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)
or 2 (Binary Input Change with Absolute Time)
or 3 (Binary Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class
(1, 2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
50 Fault Forward/Line 0,2 2 2
51 Fault Reverse/Busbar 0,2 2 2
52 51-1 0,2 2 2
53 50-1 0,2 2 2
54 51N-1 0,2 2 2
55 50N-1 0,2 2 2
56 51G-1 0,2 2 2
57 50G-1 0,2 2 2
58 51-2 0,2 2 2
59 50-2 0,2 2 2
60 51N-2 0,2 2 2
61 50N-2 0,2 2 2
62 51G-2 0,2 2 2
63 50G-2 0,2 2 2
64 60 CTS 0,2 2 2
65 46IT 0,2 2 2
66 46DT 0,2 2 2
67 47-1 0,2 2 2
68 47-2 0,2 2 2
69 46BC 0,2 2 2
70 27/59-1 0,2 2 2
71 27/59-2 0,2 2 2
72 27/59-3 0,2 2 2
73 27/59-4 0,2 2 2
74 59NIT 0,2 2 2
75 59NDT 0,2 2 2
76 81-1 0,2 2 2
77 81-2 0,2 2 2
78 81-3 0,2 2 2
79 81-4 0,2 2 2
80 Auto-reclose active 0,2 2 2
81 CB on by auto reclose 0,2 2 2
82 Reclaim 0,2 2 2
83 Lockout 0,2 2 2
86 51-3 0,2 2 2
87 50-3 0,2 2 2
88 51N-3 0,2 2 2
89 50N-3 0,2 2 2
90 51G-3 0,2 2 2
91 50G-3 0,2 2 2
92 51-4 0,2 2 2