7SR120 Technical Manual
Chapter 4 - Page 58 of 84 © 2017 Siemens Protection Devices Limited
Binary Input Points
Static (Steady-State) Object Number: 1 (Packed Format)
Change Event Object Number: 1 (w/o Time)
Static Variation reported when variation 0 requested: 1 (Binary Input w/o status)
or 2 (Binary Input with status)
Change Event Variation reported when variation 0 requested: 1 (Binary Input Change w/o Time)
or 2 (Binary Input Change with Absolute Time)
or 3 (Binary Input Change with Relative Time)
Point
Index
Description
Default Change Event
Assigned Class
(1, 2, 3 or none)
Default Variation
Static Object 1
Default Variation
Event Object 2
93 50-4 0,2 2 2
94 51N-4 0,2 2 2
95 50N-4 0,2 2 2
96 51G-4 0,2 2 2
97 50G-4 0,2 2 2
98 Cold Load Active 0,2 2 2
99 E/F Out 0,2 2 2
100 P/F Inst Protection Inhibited 0,2 2 2
101 E/F Inst Protection Inhibited 0,2 2 2
102 SEF Inst Protection Inhibited 0,2 2 2
103 Ext Inst Protection Inhibited 0,2 2 2
117 51SEF-1 0,2 2 2
118 50SEF-1 0,2 2 2
119 51SEF-2 0,2 2 2
120 50SEF-2 0,2 2 2
121 51SEF-3 0,2 2 2
122 50SEF-3 0,2 2 2
123 51SEF-4 0,2 2 2
124 50SEF-4 0,2 2 2
125 SEF Out 0,2 2 2
126 Trip Circuit Fail 1 0,2 2 2
127 Trip Circuit Fail 2 0,2 2 2
128 Trip Circuit Fail 3 0,2 2 2
129 CB Total Trip Count 0,2 2 2
130 CB Delta Trip Count 0,2 2 2
131 CB Count To AR Block 0,2 2 2
132 CB Frequent Ops Count 0,2 2 2
133 I^2t CB Wear 0,2 2 2
207 Close Circuit Fail 1 0,2 2 2
208 Close Circuit Fail 2 0,2 2 2
209 Close Circuit Fail 3 0,2 2 2
210 Close Circuit Fail 0,2 2 2
211 50BF Stage 1 0,2 2 2
212 50BF Stage 2 0,2 2 2
213 49-Alarm 0,2 2 2
214 49-Trip 0,2 2 2
215 64H 0,2 2 2
217 37-1 0,2 2 2
218 37-2 0,2 2 2
219 CB Alarm 0,2 2 2
223 SEF Forward/Line 0,2 2 2
224 SEF Reverse/Busbar 0,2 2 2