E3M140 Line module ”FD20”
108
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
26.4 Important components
I-BUS ADR
SYNOPTIK
1
ON
1
4
I-BUS SPG
SYNC
µ
P
ON
1
I-BUS
P2-LineDriver
NOTALARM
NOTBETRIEB
ASIC
I-BUS
Linienprozessor
1
2
3
4
5
6
7
8
9
SYNC-MASTER
Legend:
1 Plug-in terminals "SYNC": Synchronization of the alarm devices
2 Programming switch "SYNC-MASTER": "Synchronization alarm devices" set-
ting
on
The line module is the 'master' and sends the pulse in intervals of one second to all
line modules attached to the plug-in terminals 'SYNC' (only valid in the same station)
1
off
The line module is the ’slave’ and receives the pulse cycle from the ’master’ via the
plug-in terminals ’SYNC’
on
2
off
no function
’SYNC-MASTER’ are set to ”off” at the factory
3 Programming switch "I-BUS ADR": "I-Bus address" setting
Each element (module) connected to the I-Bus must have an individual address (num-
ber). This is set on programming switch ”I-BUS ADR”.
Maximum 16 I-Bus devices.
Function / I-Bus address Programming switch I-BUS ADR
No. 1 2 3 4 5 6
0 Module out of commission (unused) off off off off off off
1 I-Bus user number 1 on off off off off off
2 2 off on off off off off
3 3 on on off off off off
4 4 off off on off off off
5 5 on off on off off off
6 6 off on on off off off
7 7 on on on off off off
8 8 off off off on off off
9 9 on off off on off off
10 10 off on off on off off
11 11 on on off on off off
12 12 off off on on off off
13 13 on off on on off off
14 14 off on on on off off
15 15 on on on on off off
16 16 off off off off on off
’1... 6’ are set to ”off” at the factory