E3C010 Battery charging module (superseded by E3C011)
60
Building Technologies 001260_k_en_--.doc
Fire Safety & Security Products 02.2005
11.4 Important components
ASIC
I-Bus
ON
ON
S1
K1
ST1
S2
S3
F503
F502
F501
1
4
µ
P
1
1
1
2
3
4
5
6
7
Legend:
1 Fuses
F501 6,3 A/T* Battery "Positive"
F502 6,3 A/T* Battery "Negative"
F503 6,3 A/T* Battery "Center"
* Fuse with high breaking capacity (sand-filled)
2 Programming switch "S3": Set "I-Bus address"
Each element (module) connected to I-Bus must have an individual address (number).
This is set on programming switch "S3".
Maximum 16 I-Bus users.
Function / I-Bus address Programming switch S3
No. S3-1 S3-2 S3-3 S3-4 S3-5 S3-6
0 Module out of commission (unused) off off off off off off
1 I-Bus user number 1 on off off off off off
2 2 off on off off off off
3 3 on on off off off off
4 4 off off on off off off
5 5 on off on off off off
6 6 off on on off off off
7 7 on on on off off off
8 8 off off off on off off
9 9 on off off on off off
10 10 off on off on off off
11 11 on on off on off off
12 12 off off on on off off
13 13 on off on on off off
14 14 off on on on off off
15 15 on on on on off off
16 16 off off off off on off
”S3-1...6” are set to ”off” at the factory